A denial of service vulnerability exists in the Modbus...
High severity
Unreviewed
Published
Dec 1, 2025
to the GitHub Advisory Database
•
Updated Dec 1, 2025
Description
Published by the National Vulnerability Database
Dec 1, 2025
Published to the GitHub Advisory Database
Dec 1, 2025
Last updated
Dec 1, 2025
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.