Skip to content

Error in the center-tapped transformers #47

@Junjia-Yang

Description

@Junjia-Yang

Hi, first of all, thank you very much for sharing this comprehensive distribution system dataset. It has been extremely valuable for my research, and I truly appreciate the effort that went into making it publicly available.

While going through the OpenDSS transformer definitions, I noticed something that might be a typo regarding the center-tapped transformers (CTT). In the current model, they are defined as:

XHL = 2.4
XLT = 2.4
XHT = 1.6

However, in the OpenDSS examples I’ve seen, the typical configuration appears to have XHL = XHT, rather than XHL = XLT.

I just wanted to kindly check whether this was set intentionally, or if it might be a typo. It’s also possible that I’ve misunderstood something, so I would really appreciate any clarification.

Thanks again for your generous contribution and support to the community!

Best regards,
Junjia

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type

    Projects

    No projects

    Milestone

    No milestone

    Relationships

    None yet

    Development

    No branches or pull requests

    Issue actions